Skip to main content
Version: 2.0.0@Current

Inverter Configurations

Grid Parameters

Setting NameSetting CodeValue rangeUnit
Superior Intelligent Devices SN(Smart Meter、 DataLogger)dataLoggerSNWhen there is a physical connection between the inverter and the smart meter, the value is shown as the smart device's SN
Data reporting time for Superior IntelligentdataLoggerTime
Remote - LocalcommunicationModeRemote communication mode - Local communication mode
When there is no local communication mode, display "/".
Standard PowerstandardPowerkW
Firmware VersionfirmwareVersionex:V1-0127-0053
0127 is the version of ARM
0053 is the version of DSP
Master Device Sn(readonly)masterSn
BMS Sn(readonly)masterControlSn
Safety code settingssafetyCountrysee appendix
WorkMode SethybridWorkModesee appendix
Grid typeoutputModeSetting0 - Wye
1 - Delta
Battery modelbatteryTypeCodesee appendix

Grid Parameters / SOC protection settings

Setting NameSetting CodeValue rangeUnit
SOC on-grid protectiongridConnectedSocProtection1 - On
0 - Off
On-grid DODgridConnectedDischargeDepth[10.0-90.0]%
Off-grid SOC protectionoffGridSocProtection1 - On
0 - Off
Off-Grid DODoffGridDischargeDepth[10.0-90.0]%

Power Control

Setting NameSetting CodeValue rangeUnit
Export LimitantiCounterCurrentStartStop1 - On
0 - Off
Feed in GridantiReverseCurrentPowerSetting[0.0, 100.0]%
Import limitpeakLoadShiftSwitch1 - On
0 - Off
Power from gridgridMaximumCapacitySet[0.0, 650.0]kW
Export ControlsystemControl0 - Hard
1 - Soft
CT ratio settingctRatioSetting[1, 6000]
Maximum output poweroverloadModeSetting0 - Normal
1 - Overload
2 - UnderLoad

Grid Connection Parameter

Grid Connection Parameter / Protection Parameters

The protection time gain is affected by the grid frequency. The gain is 0.05 at 50Hz and 0.06 at 60Hz (The purpose is to convert it to the frequency value (Prd) and store it on the device);

Please refer to [Appendix - Safety Regulation List] to query the grid frequency corresponding to the safety regulation

Setting NameSetting CodeValue rangeUnit
10-min overvoltage protection switchtenMinOverVoltageEnable1 - On
0 - Off
10-min overvoltage protection thresholdtenMinOverVoltageThreshold[0.0,300.0]V

Grid Connection Parameter / Protection Parameters / OV/UV settings

To make it easier for customers to understand, the monitoring system converts Level-1 UV protection time, Level-1 OV protection time, Level-2 UV protection time, and Level-2 OV protection time. Customers send values in ms, and the monitoring system converts them to Prd before delivery.

Setting NameSetting CodeValue rangeUnitDescription
Level-1 UV protection thresholdfirstUnderVoltageValue[0.0, 300.0]V
Level-1 UV protection timefirstUnderVoltageTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms
Level-1 OV protection thresholdfirstOverVoltageValue[0.0, 300.0]V
Level-1 OV protection timefirstOverVoltageTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms
Level-2 UV protection thresholdsecondUnderVoltageValue[0.0, 300.0]V
Level-2 UV protection timesecondUnderVoltageTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms
Level-2 OV protection thresholdsecondOverVoltageValue[0.0, 300.0]V
Level-2 OV protection timesecondOverVoltageTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms

Grid Connection Parameter / Protection Parameters / OF/UF settings

Setting NameSetting CodeValue rangeUnitDescription
Level-1 UF protection thresholdfirstUnderFrequencyValue[45.00, 65.00]Hz
Level-1 UF protection timefirstUnderFrequencyTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms
Level-1 OF protection thresholdfirstOverFrequencyValue[45.00, 65.00]Hz
Level-1 OF protection timefirstOverFrequencyTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms
Level-2 UF protection thresholdsecondUnderFrequencyValue[45.00, 65.00]Hz
Level-2 UF protection timesecondUnderFrequencyTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms
Level-2 OF protection thresholdsecondOverFrequencyValue[45.00, 65.00]Hz
Level-2 OF protection timesecondOverFrequencyTime[1, 5000]Prd50Hz:1prd=20ms ; 60Hz:1prd=16.67ms

Grid Connection Parameter / Grid Connection Parameter

Setting NameSetting CodeValue rangeUnit
Grid connection switchreconnectionLimitEnable1 - On
0 - Off
s
Active power increase gradientslowLoadRate[0.0, 100.0]%Pn/min

Grid Connection Parameter / Grid Connection Parameter / Starting to generate power

Setting NameSetting CodeValue rangeUnit
Lower voltagevoltageLowerThresholdForNoFault[0.0, 300.0]V
Upper voltagevoltageUpperThresholdForNoFault[0.0, 300.0]V
Lower frequencyfrequencyLowerThresholdForNoFault[45.00, 65.00]Hz
Upper frequencyfrequencyUpperThresholdForNoFault[45.00, 65.00]Hz
Observation timewaitingTimeForNoFault[20, 1200]s

Grid Connection Parameter / Grid Connection Parameter / Reconnection after tripping

Setting NameSetting CodeValue rangeUnit
Lower voltagevoltageLowerThresholdForFault[0.0-300.0]V
Upper voltagevoltageUpperThresholdForFault[0.0, 300.0]V
Lower frequencyfrequencyLowerThresholdForFault[45.00, 65.00]Hz
Upper frequencyfrequencyUpperThresholdForFault[45.00, 65.00]Hz
Observation timewaitingTimeForFault[20, 1200]s

Grid Connection Parameter / Reactive Power Control

Setting NameSetting CodeValue rangeUnit
Reactive ModereactivePowerControlModesee appendix
Power factorpfPower(-1.000, 1.000]
Fixed QqParams[-60.0, 60.0]Pn%
PF curve at power point ApfCurvePowerA[0, 100.0]%
PF curve at power point BpfCurvePowerB[20.0, 100.0]%
PF curve at power point CpfCurvePowerC[20.0, 100.0]%
PF curve at point ApfPowerA[0.800, 1.000]
PF curve at point BpfPowerB[0.800, 1.000]
PF curve at point CpfPowerC[0.800, 1.000]
Q(U) Point 1 voltagequVoltage1[184.0, 230.0]V
Reactive power percent at point 1quReactive1[0.0, 60.0]%
Q(U) Point 2 voltagequVoltage2[184.0, 230.0]V
Reactive power percent at point 2quReactive2[-60.0, 60.0]%
Q(U) Point 3 voltagequVoltage3[230.0, 276.0]V
Reactive power percent at point 3quReactive3[-60.0, 60.0]%
Q(U) Point 4 voltagequVoltage4[230.0, 276.0]V
Reactive power percent at point 4quReactive4[-60.0, 0.0]%
Minimum cos(phi)rsved28110[0.1, 0.8]%
Time constant for Q(U)timeConstant[0.0, 60.0]s
Lock in powerinQuPowerThreshold[0.0, 100.0]%
Lock out poweroutQuPowerThreshold[0.0, 100.0]%
Setting NameSetting CodeValue rangeUnit
P(U) curve switchoverVoltageLoadReductionEnable1 - On
0 - Off
P(U) curve start voltagevoltage3ForPuCurve[230.0, 276.0]V
Power of P(U) curve start voltagepower3ForPuCurve[0.0, 100.0]%
P(U) curve end voltagevoltage4ForPuCurve[230.0, 276.0]V
Power of P(U) curve end voltagepower4ForPuCurve[0.0, 100.0]%
P(U) Time constant (τ)rsved28112[0.0, 60.0]s

Grid Connection Parameter / Active response to frequency deviation (FP)

Setting NameSetting CodeValue rangeUnit
Overfrequency FP curve switchoverFrequencyLoadReductionEnableForFp1 - On
0 - Off
Overfrequency thresholdoverFrequencyLoadReductionStartFrequencyForFp[50.00, 65.00]Hz
Overfrequency threshold poweroverFrequencyLoadReductionStartFrequencyPowerForFp[0.0, 100.0]%
Overfrequency end point frequencyoverFrequencyLoadReductionEndFrequencyForFp[50.00, 65.00]Hz
Overfrequency end point poweroverFrequencyLoadReductionEndFrequencyPowerForFp[0.0, 100.0]%
Overfrequency recovery thresholdrecoveryPowerFrequencyThresholdForFpOverFrequencyLoadReduction[50.00, 65.00]Hz
Overfrequency deactivation timepowerRecoveryWaitingTimeForFpOverFrequencyLoadReduction[0.800, 1.000]s
Overfrequency power recovery ratepowerRecoverySlowLoadRateForFpOverFrequencyLoadReduction[0.0, 100.0]%/min

Grid Connection Parameter / LVRT

  1. For voltage (V) related parameters below, when the monitoring system sends them to the inverter, they are multiplied by a coefficient and rounded before delivery. Therefore, when you read the values back from the device, there may be minor decimal differences compared to the values you originally sent.
  2. For example, if you set the Lock in voltage (Zero current) to 223.0V, the system sends it to the inverter as 223*22.624 = 5,045.152, which is rounded to 5,045. When reading back, 5,045/22.624 = 222.99, which rounds to 223.0V.
Setting NameSetting CodeValue rangeUnit
LVRT switchlowThroughEnable1 - On
0 - Off
Lock in voltage (Zero current)lowThroughEntryVoltage[11.5, 230]V
Point 1 voltagelowThroughVoltage1[11.5, 207]V
Point 1 protection timeprotectionTimeForLowThroughVoltage1[0, 62000]ms
Point 2 voltagelowThroughVoltage2[11.5, 207]V
Point 2 protection timeprotectionTimeForLowThroughVoltage2[0, 62000]ms
Point 3 voltagelowThroughVoltage3[11.5, 207]V
Point 3 protection timeprotectionTimeForLowThroughVoltage3[0, 62000]ms
Point 4 voltagelowThroughVoltage4[11.5, 207]V
Point 4 protection timeprotectionTimeForLowThroughVoltage4[0, 62000]ms
Point 5 voltagelowThroughVoltage5[11.5, 207]V
Point 5 protection timeprotectionTimeForLowThroughVoltage5[0, 62000]ms

Feature Parameters

Setting NameSetting CodeValue rangeUnit
Multiple Inverter RolemasterSlaveFlag1 - Slave
2 - Master
0 - Independent
On or Off-grid switchallowParallelSwitch1 - On
0 - Off
MPPT parallel connectionmpptParallelingSwitch1 - On
0 - Off
Unbalanced OutputgridConnectedUnbalancedSwitch1 - On
0 - Off
Off-grid overload reconnect delayoffGridOverload[20, 1200]s
Off-grid voltage settingoffGridVoltageSet[195.5, 264.5]V
N-PE checknpeCheckFlag1 - On
0 - Off
V

Load Management

#x:takes the rated power of the device

Setting NameSetting CodeValue rangeUnit
DO(dry connector) Function Settingsdo1Value0 - Disable
1 - External N-PE
2 - Load Management
Load ManagementloadControlMode0 - Off
1 - ManualMode
2 - SmartMode

Load Management / Manual mode

Setting NameSetting CodeValue rangeUnit
Switch StatusmanualModeRelayStatus1 - On
0 - Off

Load Management / Smart mode

Setting NameSetting CodeValue rangeUnit
Feed-in Power Control or Battery SOC ControlcontrolTypeMode30 - All off
1 - Feed-in Power Control
2 - Battery SOC Control
Feed-in Power ThresholdexportPowerThresholdMode3[0, #x]W
Consumption Power ThresholdimportPowerThresholdMode3[0, #x]W
Start SOC ThresholdstartSocMode3[0.00, 100.00]%
End SOC ThresholdrecoverySocMode3[0.00, 100.00]%
Minimum Operation HoursonceRunTimeMinMode3[0,120]&& less than Daily Max Operation Hoursmin
Daily Max Operation HoursoneDayRunTimeMaxMode3[1,1440]&& more than Minimum Operation Hoursmin

EMS Control

The following parameters can be set, but the data is null when reading. It is necessary to determine whether it takes effect through the power.

Setting NameSetting CodeValue rangeUnit
Dispatching mode of parallel systemparallelSysScheduleMode0 - Master scheduling
1 - External EMS scheduling
----
Power dispatching mode setting of parallel systemparallelSysPowerModeSetting0 - Off
1 - Total power setting
2 - Power Setting on each Phase
----
Setting of total power dispatching for the parallel systemparallelSysTotalPowerSettingOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW
Power dispatching setting of phase A for the parallel systemparallelSysPowerSettingAOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW
Power dispatching setting of phase B for the parallel systemparallelSysPowerSettingBOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW
Power dispatching setting of phase C for the parallel systemparallelSysPowerSettingCOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW
Power dispatching setting of battery for the parallel systemparallelSysBatteryPowerSettingOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW
Upstream power limit of the parallel systemparallelSysUpPowerLimitOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW
Downstream power limit of the parallel systemparallelSysDownPowerLimitOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW