Inverter Configurations

Grid Parameters

Setting NameSetting CodeValue rangeUnitcoefficient
Superior Intelligent Devices SN(Smart Meter、 DataLogger)dataLoggerSNWhen there is a physical connection between the inverter and the smart meter, the value is shown as the smart device's SN
Data reporting time for Superior IntelligentdataLoggerTime
Remote - LocalcommunicationModeRemote communication mode - Local communication mode
When there is no local communication mode, display "/".
Standard PowerstandardPowerkW
Firmware VersionfirmwareVersionex:V1-0127-0053
0127 is the version of ARM
0053 is the version of DSP
Master Device Sn(readonly)masterSn
BMS Sn(readonly)masterControlSn
Safety code settingssafetyCountrysee appendix
WorkMode SethybridWorkModesee appendix
Grid typeoutputModeSetting0 - Wye
1 - Delta
Battery modelbatteryTypeCodesee appendix

Grid Parameters / SOC protection settings

Setting NameSetting CodeValue rangeUnitcoefficient
SOC on-grid protectiongridConnectedSocProtection1 - On
0 - Off
On-grid DODgridConnectedDischargeDepth[10.0-90.0]%10
Off-grid SOC protectionoffGridSocProtection1 - On
0 - Off
Off-Grid DODoffGridDischargeDepth[10.0-90.0]%10

Power Control

Setting NameSetting CodeValue rangeUnitcoefficient
Export LimitantiCounterCurrentStartStop1 - On
0 - Off
Feed in GridantiReverseCurrentPowerSetting[0.0, 100.0]%10
Export ControlsystemControl0 - Hard
1 - Soft
CT ratio settingctRatioSetting[1, 6000]
Maximum output poweroverloadModeSetting0 - Normal
1 - Overload
2 - UnderLoad

Grid Connection Parameter

Grid Connection Parameter / Protection Parameters

The protection time gain is affected by the grid frequency. The gain is 0.05 at 50Hz and 0.06 at 60Hz (The purpose is to convert it to the frequency value (Prd) and store it on the device);

Please refer to [Appendix - Safety Regulation List] to query the grid frequency corresponding to the safety regulation

Setting NameSetting CodeValue rangeUnitcoefficient
10-min overvoltage protection switchtenMinOverVoltageEnable1 - On
0 - Off
10-min overvoltage protection thresholdtenMinOverVoltageThreshold[0.0,300.0]V10

Grid Connection Parameter / Protection Parameters / OV/UV settings

Setting NameSetting CodeValue rangeUnitcoefficient
Level-1 UV protection thresholdfirstUnderVoltageValue[0.0, 300.0]V10
Level-1 UV protection timefirstUnderVoltageTime[0, 62000]ms0.05 or 0.06
Level-1 OV protection thresholdfirstOverVoltageValue[0.0, 300.0]V10
Level-1 OV protection timefirstOverVoltageTime[0, 62000]ms0.05 or 0.06
Level-2 UV protection thresholdsecondUnderVoltageValue[0.0, 300.0]V10
Level-2 UV protection timesecondUnderVoltageTime[0, 62000]ms0.05 or 0.06
Level-2 OV protection thresholdsecondOverVoltageValue[0.0, 300.0]V10
Level-2 OV protection timesecondOverVoltageTime[0, 62000]ms0.05 or 0.06

Grid Connection Parameter / Protection Parameters / OF/UF settings

Setting NameSetting CodeValue rangeUnitcoefficient
Level-1 UF protection thresholdfirstUnderFrequencyValue[45.00, 65.00]Hz100
Level-1 UF protection timefirstUnderFrequencyTime[0, 62000]ms0.05 or 0.06
Level-1 OF protection thresholdfirstOverFrequencyValue[45.00, 65.00]Hz100
Level-1 OF protection timefirstOverFrequencyTime[0, 62000]ms0.05 or 0.06
Level-2 UF protection thresholdsecondUnderFrequencyValue[45.00, 65.00]Hz100
Level-2 UF protection timesecondUnderFrequencyTime[0, 62000]ms0.05 or 0.06
Level-2 OF protection thresholdsecondOverFrequencyValue[45.00, 65.00]Hz100
Level-2 OF protection timesecondOverFrequencyTime[0, 62000]ms0.05 or 0.06

Grid Connection Parameter / Grid Connection Parameter

Setting NameSetting CodeValue rangeUnitcoefficient
Grid connection switchreconnectionLimitEnable1 - On
0 - Off
s
Active power increase gradientslowLoadRate[0.0, 100.0]%Pn/min10

Grid Connection Parameter / Grid Connection Parameter / Starting to generate power

Setting NameSetting CodeValue rangeUnitcoefficient
Lower voltagevoltageLowerThresholdForNoFault[0.0, 300.0]V10
Upper voltagevoltageUpperThresholdForNoFault[0.0, 300.0]V10
Lower frequencyfrequencyLowerThresholdForNoFault[45.00, 65.00]Hz100
Upper frequencyfrequencyUpperThresholdForNoFault[45.00, 65.00]Hz100
Observation timewaitingTimeForNoFault[20, 1200]s

Grid Connection Parameter / Grid Connection Parameter / Reconnection after tripping

Setting NameSetting CodeValue rangeUnitcoefficient
Lower voltagevoltageLowerThresholdForFault[0.0-300.0]V10
Upper voltagevoltageUpperThresholdForFault[0.0, 300.0]V10
Lower frequencyfrequencyLowerThresholdForFault[45.00, 65.00]Hz100
Upper frequencyfrequencyUpperThresholdForFault[45.00, 65.00]Hz100
Observation timewaitingTimeForFault[20, 1200]s

Grid Connection Parameter / Reactive Power Control

Setting NameSetting CodeValue rangeUnitcoefficient
Reactive ModereactivePowerControlModesee appendix
Power factorpfPower(-1.000, 1.000]1000
Fixed QqParams[-60.0, 60.0]Pn%10
PF curve at power point ApfCurvePowerA[0, 100.0]%10
PF curve at power point BpfCurvePowerB[20.0, 100.0]%10
PF curve at power point CpfCurvePowerC[20.0, 100.0]%10
PF curve at point ApfPowerA[0.800, 1.000]
PF curve at point BpfPowerB[0.800, 1.000]
PF curve at point CpfPowerC[0.800, 1.000]
Q(U) Point 1 voltagequVoltage1[184.0, 230.0]V10
Reactive power percent at point 1quReactive1[0.0, 60.0]%10
Q(U) Point 2 voltagequVoltage2[184.0, 230.0]V10
Reactive power percent at point 2quReactive2[-60.0, 60.0]%10
Q(U) Point 3 voltagequVoltage3[230.0, 276.0]V10
Reactive power percent at point 3quReactive3[-60.0, 60.0]%10
Q(U) Point 4 voltagequVoltage4[230.0, 276.0]V10
Reactive power percent at point 4quReactive4[-60.0, 0.0]%10
Minimum cos(phi)rsved28110[0.1, 0.8]%1000
Time constant for Q(U)timeConstant[0.0, 60.0]s10
Lock in powerinQuPowerThreshold[0.0, 100.0]%10
Lock out poweroutQuPowerThreshold[0.0, 100.0]%10
Setting NameSetting CodeValue rangeUnitcoefficient
P(U) curve switchoverVoltageLoadReductionEnable1 - On
0 - Off
P(U) curve start voltagevoltage3ForPuCurve[230.0, 276.0]V10
Power of P(U) curve start voltagepower3ForPuCurve[0.0, 100.0]%10
P(U) curve end voltagevoltage4ForPuCurve[230.0, 276.0]V10
Power of P(U) curve end voltagepower4ForPuCurve[0.0, 100.0]%10
P(U) Time constant (τ)rsved28112[0.0, 60.0]s10

Grid Connection Parameter / Active response to frequency deviation (FP)

Setting NameSetting CodeValue rangeUnitcoefficient
Overfrequency FP curve switchoverFrequencyLoadReductionEnableForFp1 - On
0 - Off
Overfrequency thresholdoverFrequencyLoadReductionStartFrequencyForFp[50.00, 65.00]Hz100
Overfrequency threshold poweroverFrequencyLoadReductionStartFrequencyPowerForFp[0.0, 100.0]%10
Overfrequency end point frequencyoverFrequencyLoadReductionEndFrequencyForFp[50.00, 65.00]Hz100
Overfrequency end point poweroverFrequencyLoadReductionEndFrequencyPowerForFp[0.0, 100.0]%10
Overfrequency recovery thresholdrecoveryPowerFrequencyThresholdForFpOverFrequencyLoadReduction[50.00, 65.00]Hz100
Overfrequency deactivation timepowerRecoveryWaitingTimeForFpOverFrequencyLoadReduction[0.800, 1.000]s
Overfrequency power recovery ratepowerRecoverySlowLoadRateForFpOverFrequencyLoadReduction[0.0, 100.0]%/min10

Grid Connection Parameter / LVRT

The purpose of the gain is to allow the registers to store integers. The sent value multiplied by the gain of 22.624, and the result is rounded up to the nearest whole number.

Setting NameSetting CodeValue rangeUnitcoefficient
LVRT switchlowThroughEnable1 - On
0 - Off
Lock in voltage (Zero current)lowThroughEntryVoltage[11.5, 230]V22.624
Point 1 voltagelowThroughVoltage1[11.5, 207]V22.624
Point 1 protection timeprotectionTimeForLowThroughVoltage1[0, 62000]ms2
Point 2 voltagelowThroughVoltage2[11.5, 207]V22.624
Point 2 protection timeprotectionTimeForLowThroughVoltage2[0, 62000]ms2
Point 3 voltagelowThroughVoltage3[11.5, 207]V22.624
Point 3 protection timeprotectionTimeForLowThroughVoltage3[0, 62000]ms2
Point 4 voltagelowThroughVoltage4[11.5, 207]V22.624
Point 4 protection timeprotectionTimeForLowThroughVoltage4[0, 62000]ms2
Point 5 voltagelowThroughVoltage5[11.5, 207]V22.624
Point 5 protection timeprotectionTimeForLowThroughVoltage5[0, 62000]ms2

Feature Parameters

Setting NameSetting CodeValue rangeUnitcoefficient
Multiple Inverter RolemasterSlaveFlag1 - Slave
2 - Master
0 - Independent
On or Off-grid switchallowParallelSwitch1 - On
0 - Off
MPPT parallel connectionmpptParallelingSwitch1 - On
0 - Off
Unbalanced OutputgridConnectedUnbalancedSwitch1 - On
0 - Off
Off-grid overload reconnect delayoffGridOverload[20, 1200]s1
Off-grid voltage settingoffGridVoltageSet[195.5, 264.5]V10
N-PE checknpeCheckFlag1 - On
0 - Off
V10

Load Management

#x:takes the rated power of the device

Setting NameSetting CodeValue rangeUnitcoefficient
DO(dry connector) Function Settingsdo1Value0 - Disable
1 - External N-PE
2 - Load Management
Load ManagementloadControlMode0 - Off
1 - ManualMode
2 - SmartMode

Load Management / Manual mode

Setting NameSetting CodeValue rangeUnitcoefficient
Switch StatusmanualModeRelayStatus1 - On
0 - Off

Load Management / Smart mode

Setting NameSetting CodeValue rangeUnitcoefficient
Feed-in Power Control or Battery SOC ControlcontrolTypeMode30 - All off
1 - Feed-in Power Control
2 - Battery SOC Control
Feed-in Power ThresholdexportPowerThresholdMode3[0, #x]W
Consumption Power ThresholdimportPowerThresholdMode3[0, #x]W
Start SOC ThresholdstartSocMode3[0.00, 100.00]%100
End SOC ThresholdrecoverySocMode3[0.00, 100.00]%100
Minimum Operation HoursonceRunTimeMinMode3[0,120]&& less than Daily Max Operation Hoursmin
Daily Max Operation HoursoneDayRunTimeMaxMode3[1,1440]&& more than Minimum Operation Hoursmin

EMS Control

The following parameters can be set, but the data is null when reading. It is necessary to determine whether it takes effect through the power.

Setting NameSetting CodeValue rangeUnitcoefficient
Dispatching mode of parallel systemparallelSysScheduleMode0 - Master scheduling
1 - External EMS scheduling
---------------
Power dispatching mode setting of parallel systemparallelSysPowerModeSetting0 - Off
1 - Total power setting
2 - Power Setting on each Phase
---------------
Setting of total power dispatching for the parallel systemparallelSysTotalPowerSettingOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10
Power dispatching setting of phase A for the parallel systemparallelSysPowerSettingAOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10
Power dispatching setting of phase B for the parallel systemparallelSysPowerSettingBOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10
Power dispatching setting of phase C for the parallel systemparallelSysPowerSettingCOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10
Power dispatching setting of battery for the parallel systemparallelSysBatteryPowerSettingOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10
Upstream power limit of the parallel systemparallelSysUpPowerLimitOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10
Downstream power limit of the parallel systemparallelSysDownPowerLimitOnly for the Master-Slave Parallel system, and the External EMS can schedule system power through the MasterkW10